- Side By Side Study Of Energy Use And Moisture Control
                        Comparing Standard Split System Air Conditioning And A
                        Coleman® Prototype Heat Pump, Bousier
                    City, LA 
 
 
In
                      2001, the BAIHP team conducted research on two homes to
                      define how tight ducts and a prototype Coleman® heat
                    pump (proprietary technology) affect energy use and moisture
                    control in a hot, humid climate. FSEC, in collaboration with
                    Fleetwood Homes, York International Manufactured Housing
                    Division (now Stylecrest Sales), and Coleman®, monitored
                    two nearly identical side-by-side homes in Bossier City,
                    Louisiana. The homes contained different air conditioning
                    systems. House A used a standard split air conditioner, while
                    House B used the Coleman® prototype unit (a more efficient,
                  two-speed split air conditioner). 
Figure 45 shows the reduced power draw of the two-speed
                    compressor (green, dotted line) over a 24-hour period on
                    September 2, 2000. With the unit operating at low-speed for
                    most of the day, the cooling energy savings were 28% when
                    compared to the energy use in House A. Average daily cooling
                    energy was reduced by about 12% over the monitored period.
                    An added benefit of the two-speed air conditioner was 20%
                    greater moisture removal on days with an outdoor dewpoint
                    above 60 F. 
 | 
 
 Figure
                                45  Power draw
                        over a  
                      24-hour period, September 2, 2000.  | 
 
  Savings from Duct Repair and POS Ventilation: In addition
                    to comparing one house to the other, the BAIHP team also
                    compared home performance before and after ductwork and ventilation
                  system changes were made. 
To make the comparison, duct and other
                      leaks were sealed in both houses until the two were equally
                      airtight. The ventilation method in each home also was
                    changed from exhaust-only to a positive pressure system (POS).
                    With exhaust-only ventilation, bathroom fans removed stale
                        air from the home which caused fresh air to be pulled
                        in through the building envelope. To simulate occupant
                        use, two bath exhaust fans were operated by a timer for
                    three hours in the morning and six hours in the evening. 
In contrast to exhaust ventilation, the POS system introduced
                    a small amount of fresh air on the return side of the air conditioning
                    cooling coil. A POS system was installed in each home at the
                    same time the ducts were repaired. Subsequent monitoring looked
                    at the effects of this alternate ventilation system. Tightening
                    the ducts and installing a POS ventilation system resulted
                    in an 18% and 37% cooling savings in the two homes. Only about
                    2% of these savings were attributable to the ventilation system
                    change, the remaining savings are a result of duct repair.
 
 | 
 
  Figure 45  
                        WSU
                      Energy House
                      in Olympia, WA   | 
 
  This 2600 ft 2 home was built beyond SGC standards and incorporates
                    Energy Star lighting and appliances. The home (Figure
                    45) has received significant national exposure through
                    WSU campus and alumni newsletters, tours, the BAIHP website,
                    and local and trade media including an article in the Automated
                  Builder magazine and a feature by KING 5 News of Seattle.  
WSU staff uses the house to try out innovative technologies
                    and testing methods.  
In
                    the 5th budget period, BAIHP staff developed a moisture case
                    study based on research at the WSU Energy House, published
                    under a separate Building America project. The WSU Energy
                    House has been monitored since 2000.  Collected monitoring
                    data includes weather, temperature, humidity, CO 2, CO, and
                    eight differential pressures.   Energy use data
                    is being collected for water heating, laundry, fireplace
                    and heating, ventilating, and air conditioning (HVAC).  Data
                    from the house is available on the BAIHP web page (under
                    Current Data) and has been presented to the building science,
                    indoor air quality (IAQ) and HVAC research communities at
                    conferences sponsored by ASHRAE, Air Infiltration and Ventilation
                    Center (in the UK), HUD/NIST, NFPA, and
                    BTECC. (See also Appendix D, WSU) 
Working
                      with Ecotope, ASHRAE, and the Energy Conservancy, BAIHP
                      staff conducted “Delta Q” and “nulling” duct
                    leakage tests in 2001.  Follow up pressure tests and
                    analysis of test data conducted in 2002 indicate these tests
                    are effective methods of measuring duct leakage in manufactured
                    homes, and may be included in the upgrades to the National
                    Fire Protection Association-501 standards for manufactured
                    homes. 
Blower door and duct leakage testing indicate very good
                    whole house and duct airtightness (2.4 ACH50 and 61.6 CFM50
                    out). Tracer gas testing demonstrated that the use of a furnace-based
                    intake damper does not change the leakage rate of the home. 
- Zero Energy Manufactured Home (ZEMH) 
 
 
 | 
 
 Figure
                                  46: Zero Energy  
                        Manufactured Home, on site
                                  at  
                      the Nez Perce Fish Hatchery   | 
 
  BPA,
                      working with BAIHP staff in Idaho and Washington, provided
                      funding for the most energy efficient manufactured home
                      in the country. The RFP was sent to 18 Northwest manufacturers;
                      Kit HomeBuilders West of Caldwell, Idaho was selected as
                      the manufacturer of the home. BAIHP staff solicited 24
                      industry partners to provide energy efficient building
                      components, including Icynene wall, floor and roof insulation,
                      a low-cost HUD-approved solar system, sun-tempered solar
                      design, and Energy Star© windows,
                      appliances and lighting. Partners include Building America
                      Team members such as Flexible Technologies, Icynene and
                  LaSalle. Complete list of specifications provided in Table 24. 
The ZEMH (Figure 46) was built in Year 4 along
                    with a control home. The ZEMH was displayed at the 2002 Spokane
                    County Interstate Fair before siting at the Nez Perce tribal
                    fish facility near Lewiston Idaho. Blower door and duct leakage
                    tests at the plant and on-site indicate that this is the
                    tightest home ever tested by BAIHP staff.  
Working with FSEC and BPA, BAIHP staff installed monitoring
                    equipment for the ZEMH. Monitoring began in the 5th budget
                    period and includes the following: 
- Total electric use from grid
 
- Resistance elements in heat pump
 
- Heat pump compressor and fan motors
 
- Water heating equipment, including gallons used
 
- PV energy production (ZEMH)
 
 
TABLE
                              24 Zero Energy Manufactured Home (ZEMH)  
                          and Base
                        Case Home (Control)  | 
 
 Component   | 
 ZEMH   | 
 Base   | 
 
 Wall Structure   | 
 2x6 ft, 16 in on center   | 
 Same   | 
 
 Wall Insulation   | 
 R21 foam-spray   | 
 R21 batt   | 
 
 Floor Structure   | 
 2x8 ft, 16 in on center   | 
 Same   | 
 
 Floor Insulation   | 
 R33 (R22 Foam + R11 batt)   | 
 R33 Blown Cellulose   | 
 
 Vented crawl space wall   | 
 R14 foil faced foam   | 
 None   | 
 
 Roof/Attic Structure and
                          Finish   | 
 16
                            in on center  
40
                            lb roof load  
4/12
                            pitch metal roofing  
 | 
 24
                            in on center  
Standard
                            30 lb roof load  
Same
                            pitch and finish  
 | 
 
 Roof/Attic Insulation   | 
 R49 foam   | 
 R33 blown cellulose   | 
 
 Window/Floor area ratio   | 
 12%   | 
 Same   | 
 
 Windows   | 
 Vinyl Frame, Argon filled,
                          low-e, Energy Star Approved   | 
 Same   | 
 
 Window Shading   | 
 Dual blinds, heavy drapes,
                          awnings   | 
 Single blinds, light drapes   | 
 
 Doors   | 
 U=0.2 metal, foam w/thermal
                          break   | 
 Same   | 
 
 Solar   | 
 Solar
                            ready design (mounts, flashings and electrical chase)  
4.2
                            kW peak rated PV system with a 4 kW inverter and
                            12 kWh battery array  
 | 
 None   | 
 
 HVAC   | 
 2
                            ton unitary air-source heat pump  
12
                            seer, 7.8 HSPF  
 | 
 Same   | 
 
 Zone heat   | 
 150 W Radiant Panel in
                          kitchen   | 
 None   | 
 
 Ducts and cross over   | 
 R8
                            crossover  
Flex
                            Flow crossover system  
Mastic
                            with screws  
More
                            efficient duct design  
 | 
 R8
                            crossover  
Sheet
                            metal elbows  
Standard
                            foil tape  
 | 
 
 Lighting   | 
 100% Energy Star T8 and
                          CFL fixtures   | 
 T12 and Incandescent fixtures   | 
 
 Appliances   | 
 Energy Star washer and
                          dryer, refrigerator, dishwasher   | 
 Standard equipment   | 
 
 Whole House Ventilation   | 
 Heat Recovery Ventilator
                          w/HEPA, continuous operation (turned off in 8/04)   | 
 Quiet (low-sone) Energy
                          Star exhaust fan, continuous operation   | 
 
 Spot Ventilation   | 
 Energy Star bath fans,
                          std. Kitchen fan   | 
 Quiet (low-sone) bath
                          fans, std. Kitchen fan   | 
 
 Ceiling Fans   | 
 Energy Star with dimmable
                          CFL   | 
 Standard with Incandescent
                          bulbs   | 
 
 Domestic Hot Water   | 
 PV controlled, active
                          anti-freeze solar water system, with 80 gallon storage,
                          and 64 ft 2 of collector area solar pre-heat tank (pre-plumbed),
                          40 gallon standard tank EF=0.93   | 
 EF=0.88 standard electric   | 
 
 Air Sealing   | 
 Wrap
                            with tape flashing  
Marriage
                            line gasket (new product)  
Penetrations
                            sealed with foam insulation  
 | 
 Wrap
                            without tape flashing  
Standard
                            practice marriage line sealing  
 | 
 
 Air/Vapor Barrier   | 
 Walls
                            and Ceiling: Painted Drywall  
Floor:
                            Floor decking  
 | 
 Same   | 
 
 
Data logger collects 15 minute data from wired sensors and
                    transmits daily to the host computer at FSEC via modem. Summary
                    data reports are available at www.baihp.org under “Current
                    Data.” Plug-type loggers were installed in mid March
                    2003 to sub-meter the energy use of the refrigerator, freezer
                    and clothes washer in each home, as well as the radiant heat
                    panel and HRV in the ZEMH. Data from these loggers was collected
                    by occupant readings in mid-December 2003. 
Preliminary findings  
Measured
                      net energy use of the ZEMH 6% is lower than the base home,
                      not normalized for occupant behavior. This also does not
                      take into account the fact that the ZEMH’s
                    PV system was only fully operational for one month. 
The ZEMH required 45% less space heating energy, possibly
                    due to improved building envelope measures, and the lack
                    of consistent HRV operation. 
The measured envelope leakage in the ZEMH was 2.0 ACH50,
                    much lower than the base home (indeed, lower than any other
                    NEEM home tested in the field) and substantially tighter
                    than typical HUD code homes.  
The ZEMH total duct leakage was 46% lower than the base
                    home; leakage to the outside was 405% lower than the base
                    home. The BAIHP staff speculates that the unprecedented low
                    leakage to the outside value is the result of the ducts in
                    the ZEMH being located within the conditioned space, and
                    effectively within the pressure envelope of the home, surrounded
                    as they are by foam insulation. 
The solar water heating system in the ZEMH provides most,
                    if not all of the hot water needed during the summer months,
                    and roughly 45% of the total hot water demand. The PV system
                    with net metering provides 38% of the total ZEMH energy use.  
The
                      project highlights the importance of occupant choices and
                      behavior on the performance of energy efficient housing.
                      Based on the preliminary monitoring data and occupant surveys,
                      the behavior patterns of the ZEMH occupants are not themselves “energy
                    efficient”. These patterns create the appearance of
                    a less efficient home. On the other hand, the behavior of
                    the ZEMH occupants may shorten the payback for the innovative
                    technologies of the ZEMH. 
BAIHP staff also performed a benchmarking analysis on the
                    ZEMH, as part of the overall benchmarking effort. The ZEMH
                    reached a level of 60% above the NREL prototype, which indicates
                    the difficulty of obtaining a high benchmarking score. 
- Manufactured Housing Indoor Air Quality Study 
 
 
In the spring of 2003, BAIHP initiated a study with Palm
                    Harbor Homes (PHH) to evaluate the energy savings from a
                    Building America Manufactured Home, compared to a standard
                  Palm Harbor Home. 
These
                      two homes were built in the fall and set up on PHH’s
                    model center in Plant City, Florida.  
The monitoring plan called for measurements of volatile
                    organic chemical (VOCs) levels, air conditioning energy use
                    and associated indicators such as indoor and outdoor conditions.
                    Both homes have split system air conditioners, SEER 15 in
                    the BA model, and SEER 10 in the Base Case model. 
The two homes were instrumented in November, however, due
                    to a PHH phone service conflict, no data was taken during
                    this budget period. Data collection is expected to commence
                    in May of 2004.  
VOC measurements were conducted in collaboration with LBNL.
                    The VOC data revealed significantly higher VOC levels in
                    the Building America home than in nearby control models of
                    a similar age. Normally, PHH would move furniture in from
                    a previous model, but in an effort to ensure high quality
                    in the BA model, PHH purchased all new, all wood furniture.
                    This is believed to be the source of VOCs in the BA model.
                    BAIHP and LBNL researchers will work to verify what caused
                    the elevated VOC level in the next budget cycle. 
- Manufactured Housing Laboratory – Ventilation
                      Studies 
 
 
Ventilation Study 
The MHLab (Figure 47) is a research
                      and training facility of 1600 ft 2. This Energy Star® manufactured
                    home has two separate heating and cooling systems:  
1. An overhead duct system connected to a package unit air
                        conditioner with electric resistance heating. 
2. A floor-mounted duct system connected to a split system
                        air conditioner, also with electric resistance heating.  
  Only the floor mounted duct system was used in these ventilation
                    experiments. 
 Introduction  
 | 
 
 Figure 47 Manufactured Housing Laboratory
                                at FSEC (above and below) was site for study of six
                      residential ventilation systems.   | 
 
 | 
 
 
Ventilation is a HUD code requirement. The goal of ventilation
                    is to add fresh air to the home. This may be accomplished
                    by supplying outside air to the house or mechanical system,
                    exhausting air from the house (which consequently pulls air
                    into the house through joints in the walls, floor, and ceiling),
                  or a combination of the two.  
Supply based ventilation tends to slightly pressurize the
                    home whereas exhaust based ventilation does the opposite
                    slightly depressurizing the house. The disadvantage of supply
                    based ventilation is that it forces conditioned air into
                    the floor, wall, and ceiling cavities, possibly leading to
                    condensation or mold growth in cold climates and during the
                    heating season. Likewise the disadvantage of exhaust systems
                    is that they pull unconditioned outside through the floor,
                    wall, and ceiling cavities into the conditioned space, possibly
                    leading to condensation, mold growth, or uncomfortably high
                    indoor humidity levels in hot and hot-humid climates and
                    during the cooling season. The six residential ventilation
                    strategies evaluated are described in Table 25. 
House Operation and Experimental Procedure  
Occupancy Simulation: Automated, computer controlled
                    devices, such as appliances, showers, and lighting, simulate
                    the sensible/latent heat generation and carbon dioxide (CO
                    2) production of a family of four persons with periodic showers,
                    cooking and cleaning.  
The simulated latent occupancy load from breathing,
                  bathing, cooking, and laundry was achieved by adding 14 to
                  15 pounds of water per day based on documentation of "average" household
                  operation based on ORNL research conducted by Jeff Christian.
                  Water vapor was injected into the space using a vaporizer at
                  a rate of approximately 0.4 lbs per hour continuous and an
                  additional 0.4 lbs per hour during the evening hours. 
 
 
 Table
                            25 Ventilation Strategies Studied in the MHLab   | 
 
 Case  
                      (Name)  
 | 
 Strategy   | 
 Description   | 
 
 # 1  
                        (None).  
 | 
 No mechanical ventilation   | 
 Base Case scenario included only the
                          heating and cooling system of the home with no outside
                          air (OA) ventilation.   | 
 
 # 2  
                        (Spot)  
 | 
 Spot ventilation (exhaust only)   | 
 Bathroom and kitchen exhaust fans.
                          Operation scheduled for 30 minutes after a simulated
                          moisture producing event such as a shower or oven use.   | 
 
 # 3  
                        (OA)  
 | 
 Outside air (supply based)   | 
 Dedicated, filtered outside air duct
                          to return plenum when the heating or cooling system
                          is operating. Quantity of ventilation air provided
                          depends on air handler run-time.   | 
 
 # 4 (Dehumid)   | 
 Outside Air plus 10/20 Cycle and Dehumidification
                          (Supply Based)   | 
 Same
                            as #3, except with an added air handler fan controller
                            (10-minute “on” -
                          20-minute “off” minimum duty cycle). Provides
                          scheduled ventilation when no cooling or heating is
                          called for. A stand alone room dehumidifier (set to
                          approximately 50% RH) located in vicinity of the return
                          air grill.   | 
 
 # 5  
                        (10/20 Cycle)  
 | 
 Outside Air plus 10/20 cycle (Supply
                          Based)   | 
 Same as #4, except without the room
                          dehumidifier.   | 
 
 # 6 (ERV1) (ERV2)   | 
 Energy recovery ventilator (ERV1, ERV2)   | 
 Two different enthalpy transfer media
                          were used. Outside air was drawn in through the ERV
                          at a rate to meet the ventilation requirements.   | 
 
 # 7  
                        (Hstat)  
 | 
 Outside Air plus Humidistat (Supply
                          Based)   | 
 This is a modified air handler fan
                          speed control. When dehumidification is needed, the
                          air handler fan is operated at lowest speed for enhanced
                          latent control. A higher speed is selected when sensible
                          cooling is needed. Ventilation air supplied via an
                          outside air duct, with air handler fan operation controlled
                          as in #4.   | 
 
 
Ventilation Rate:  Researchers conducted whole house
                    air tightness tests using sulfur hexafluoride as a tracer gas
                    for a decay analysis (Figure 48) to determine if each
                    ventilation strategy met the ASHRAE 62-2 Ventilation Standard
                    during the test period. The spot ventilation strategy (#2)
                    did not meet the standard on a daily basis as the runtime was
                    not long enough. The outside air method (#3) was marginal in
                    meeting the standard. Strategies #4-#7 met the standard.  
 | 
 
 Figure
                                  48 Results of
                                  tracer gas decay testing indicating operational
                                  infiltration  
        (house not under test pressure) rates measured for each ventilation strategy.  
        ASHRAE Standard 62.2 was the target ventilation rate, not met by Spot
        or  
        OA strategies. Note: Wind speed averaged over 2 hour infiltration test.  | 
 
 
Whole House and Duct Air Tightness: The average
                    whole house air leakage (CFM50) was 1224 (ACH50 of 5.4).
                    The target normalized duct leakage is Qn #6%, where Qn=CFM25/conditioned
                    area, this is the same as the duct leakage target in the
                    Manufactured Home Energy Star program. The total duct system
                    leakage in the MHLab Qn total=5% (CFM25 total = 75) with
                    leakage to the outside measured to be Qn (out)=3% (CFM25
                  out = 45), well under the leakage target. 
Interior temperature and relative humidity: A digital
                      thermostat maintained interior temperature at 75 degrees
                      Fahrenheit. Interior temperature and relative humidity
                    sensors are located on the same wall as the thermostat, at
                    approximately the same height from the floor. Dedicated interior
                    relative humidity control was only available with the dehumidifier
                      strategy, and was a byproduct of cooling coil operation
                    in the other strategies.  
Cooling/ventilation power usage  
With all mechanical ventilation systems, additional energy
                    use from both increased conditioning loads and fan (if present)
                    power is expected. The split system with the floor duct system
                    is a 12 SEER system with a rated cooling capacity of 30.2
                    kBtu. The ventilation strategies that required the use of
                    the air handler fan, an energy recovery ventilator, or the
                    dehumidifier had the energy use added to the cooling energy.
                    The dehumidifier strategy did use the most energy for cooling;
                    however, it should be noted that this test occurred during
                    the hottest ambient conditions. 
Table
                      26 Average Ambient and Building Conditions  | 
 
 | 
 Case 1 None   | 
 Case 2 Spot   | 
 Case 3 OA   | 
 Case
                      4 Dehumid   | 
 Case 5 10/20   | 
 Case 6 ERV1   | 
 Case 6 ERV2   | 
 Case 7 Hstat  | 
 
 Indoor
                      Temp (°F)   | 
 74.5°   | 
 74.5°   | 
 74.7°   | 
 74.9°  | 
 74.0°   | 
 74.1°   | 
 74.4°   | 
 74.8°   | 
 
 Indoor
                      Temp Max (°F)   | 
 75.0°   | 
 75.2°   | 
 75.5°   | 
 76.0°  | 
 75.0°   | 
 74.9°   | 
 75.4°   | 
 76.0°   | 
 
 Indoor RH (%)   | 
 49.2%   | 
 45.7%   | 
 49.5%   | 
 47.9%   | 
 49.1%   | 
 47.8%   | 
 47.2%   | 
 45.7%   | 
 
 Indoor
                      Dewpoint (°F)   | 
 52.4°   | 
 54.2   | 
 54.5   | 
 53.9   | 
 53.7   | 
 53.1   | 
 53.0   | 
 52.4   | 
 
 Outside
                      Temp (°F)   | 
 78.6°   | 
 78.6°   | 
 78.4°   | 
 82.1°  | 
 79.8°   | 
 79.3°   | 
 80.8°   | 
 79.2°   | 
 
 Outside RH (%)   | 
 89.2%   | 
 79.5%   | 
 87.7%   | 
 83.4%   | 
 87.0%   | 
 90.0%   | 
 86.9%   | 
 88.1%   | 
 
 Δ Temp (°F)   | 
 4.3°   | 
 4.0°   | 
 3.7°   | 
 7.1°  | 
 5.8°   | 
 5.1°   | 
 6.5   | 
 4.4   | 
 
 Δ Dewpoint (°F)   | 
 18.6°   | 
 20.7°   | 
 19.5°   | 
 22.4°  | 
 21.4°   | 
 22.7°   | 
 23.3°   | 
 22.6°   | 
 
 Solar Rad. (kWh/m 2)   | 
 53.5   | 
 107.3   | 
 68.9   | 
 76.3   | 
 86.8   | 
 66.3   | 
 101.9°   | 
 77.1°   | 
 
 Rainfall (Inches)   | 
 3.6   | 
 0.5   | 
 4.7   | 
 0.1   | 
 4.0   | 
 5.1   | 
 3.2   | 
 4.9   | 
 
 Condensate (lbs)   | 
 617   | 
 905   | 
 920   | 
 1131   | 
 1118   | 
 1034   | 
 1685   | 
 1282   | 
 
 Δ P
                      WRT Out (Pa)   | 
 -0.2   | 
 0   | 
 0.1   | 
 0.4   | 
 0   | 
 -0.2   | 
 -0.2   | 
 0.1   | 
 
 Minimum RH   | 
 42.1%   | 
 38.8%   | 
 45.8%   | 
 46.2 %  | 
 46.3%   | 
 44.2%   | 
 39.3%   | 
 39.7%   | 
 
 Maximum RH   | 
 53.3%   | 
 55.2%   | 
 53.2%   | 
 51.0 %  | 
 58.4%   | 
 64.8%   | 
 53.0%   | 
 61.4%   | 
 
 Mean RH   | 
 46.1%   | 
 49.2%   | 
 49.5%   | 
 47.9 %  | 
 49.0%   | 
 47.8%   | 
 47.2%   | 
 45.7%   | 
 
 RH Standard Deviation   | 
 1.272   | 
 1.471   | 
 1.673   | 
 0.845   | 
 1.231   | 
 2.194   | 
 2.108   | 
 3.07   | 
 
 RH Range   | 
 11.2 %   | 
 16.3 %   | 
 7.4 %   | 
 4.8 %  | 
 12.1 %   | 
 20.6 %   | 
 13.7 %   | 
 21.7 %   | 
 
 
 Findings  
The
                      cooling energy required to maintain the 75°F interior
                    set-point appeared to vary as a result of the temperature
                    difference across the envelope (Table 26). A linear regression
                    analysis was performed to compare energy use of the ventilation
                    strategies as a function of temperature difference across
                    the envelope (Table 27). The power use at the average temperature
                    difference of five degrees Fahrenheit is shown in bold. 
- Case 4, the dehumidifier system, has the highest average
                      power at 1592 watts.
 
- Case 7 (humidistat controlled fan speed or Hstat) is
                      second highest at 1485 watts. 
 
- Case 5 (10/20 cycle controller) used the least power
                      at 1315 watts. 
 
 
As might be expected, interior relative humidity had the
                    least variance with the dehumidification system with a low
                    of 46% and a high of 51% (Table 26 and Figure 49).
                    The best performing system, Case 4 (10/20 cycle plus dehumidifier),
                    was able to maintain the relative humidity at a nearly constant
                    level for almost 80% of the test period. The next best performer
                    was Case 2 (spot ventilation). Humidity levels during the
                    test period are graphed in Figure 49.  
Table 27
                          Cooling and ventilation power (watts) usage as a function
                          of temperature difference across the building envelope  | 
 
ΔTemp
                            (°F)   | 
 Case
                            1 None   | 
 Case
                            2 Spot   | 
 Case
                            3 OA  
 | 
 Case
                            4 Dehumid   | 
 Case
                            5 10/20   | 
 Case
                            6   | 
 Case
                            7 Hstat   | 
 
ERV1   | 
 ERV2   | 
 
-5  | 
487  | 
499  | 
475  | 
499  | 
411  | 
459  | 
367  | 
526  | 
 
0  | 
924  | 
911  | 
949  | 
1046  | 
863  | 
915  | 
880  | 
1006  | 
 
5   | 
1361   | 
1324   | 
1424   | 
1592   | 
1315   | 
1370   | 
1393   | 
1485   | 
 
15  | 
2236  | 
2150  | 
2372  | 
2685  | 
2219  | 
2280  | 
2418  | 
2443  | 
 
 
 
  Figure
                                  49 Average
                                  hourly relative humidity profiles for each
                                  strategy   | 
 
 | 
 | 
 
 | 
 | 
 
 | 
 | 
 
 | 
 | 
 
 
 Conclusions  
The
                      operation of a correctly sized air conditioning system
                      with a supplemental dehumidification system to pre-condition
                    the outside air and provide additional dehumidification of
                    the space appears to provide the best interior humidity control
                    (Table 26, in bold) with only a slight increase in energy
                    usage – about 200 watts (Table 27). This is represented
                    by Case 4 of this study. Only this strategy was able to maintain
                    the interior humidity conditions in a range of less than
                    5% (Table 27, in italics).  
Though
                      all of the strategies did provide some humidity control
                      over the test period, it is most likely a result of the
                      run time afforded by the correctly sized air conditioning
                      system and the consistent simulated interior sensible load.
                      When an air conditioning system operates for extended periods
                      of time, the removal of moisture from the air stream is
                      enhanced (Khattar, Swami & Ramanan
                    1987). 
Additional
                      testing with other ventilation strategies in the MHLab
                      will be undertaken in the next budget period. 
  |