- Air Handler Air Tightness Study 
 
 
 To determine the impact of air handler location
                    on heating and cooling energy use, researchers measured the
                    amount of air leakage in air handler cabinets, and between
                    the air handler cabinet and the return and supply plenums.
                    To assess this leakage, testing was performed on 69 air conditioning
                    systems. Thirty systems were tested in the 2001 and 39 in
                    2002. The 69 systems were tested in 63 Florida houses (in
                    six cases, two air handlers were tested in a single house)
                    located in seven counties across the state - four in Leon
                    County in or near Tallahassee, 17 in Polk County, three in
                    Lake County, 13 in Orange County, one in Osceola County,
                    two in Sumter County, and 29 in Brevard County. All except
                    those in Leon County are located in central Florida. Construction
                    on all houses was completed after January 1, 2001, and most
                    homes were tested within four months of occupancy.  
 In each case, air leakage (Q 25) at the air handler and
                    two adjacent connections was measured. Q 25 is the amount
                    of air leakage which occurs when the ductwork or air handler
                    is placed under 25 Pa of pressure with respect to its surrounding
                    environment. Q 25 also can be considered a measurement of
                    ductwork perforation.  
 To obtain actual air leakage while the system operated,
                    it was necessary to measure the operating pressure differential
                    between the inside and outside of the air handler and adjacent
                    connections. In other words, it was necessary to know the
                    perforation or hole size and the pressure differential operating
                    across that hole. By determining both Q 25 and operating
                    pressure differentials, actual air leakage into or out of
                    the system was calculated.  
 Field Testing Leakage Parameters  
 Testing was performed on 69 air conditioning systems to
                    determine the extent of air leakage from air handlers and
                    adjacent connections. Testing and inspection was performed
                    to obtain:  
-  Q 25 in the air handler, Q 25 at the connection to the
                      return plenum, and Q 25 at the connection to the supply
                      plenum. 
 
-  Operating pressure at four locations - the return plenum
                      connection, in the air handler before the coil, in the
                      air handler after the coil, and at the supply plenum connection. 
 
-  Return and supply air flows were measured with a flow
                      hood. Air handler flow rates were measured with an air
                      handler flow plate device (per ASHRAE Standard 152P methodology). 
 
-  Overall duct system and house airtightness in 20 of
                      the 69 homes. 
 
-  Cooling and heating system capacity based on air handler
                      and outdoor unit model numbers. 
 
-  The location and type of filter. 
 
-  Dimensions and surface area of the air handler cabinet. 
 
-  The fractions of the air handler under negative pressure
                      and under positive pressure. 
 
-  The types of sealants used at air handler connections. 
 
-  Estimated portion of the air handler
                        leak area that was sealed “as found.” 
 
 
 Air
                    Handler Leakage  
 | 
 
  Figure
                                64  Thermograph
                            of air  
                          being drawn from the attic to the  
                          air handler
                    in a Florida house   | 
 
 
Leakage in the air handler cabinet averaged 20.4 Q 25 in
                    69 air conditioning systems. Leakage at the return and supply
                    plenum connections averaged 3.9 and 1.6 Q 25, respectively.
                    Using the operating pressures in the air handler and at the
                    plenum connections, these Q 25 results convert to actual
                    air leakage of 58.8 CFM on the return side (negative pressure
                    side) and 9.3 CFM on the supply side (positive pressure side).
                    The combined return and supply air leakage in the air handler
                    and adjacent connections represents 5.3% of the system air
                    flow (4.6% on the return side and 0.7% on the supply side).
                    This is a concern, when considering that a 4.6% return leak
                    from a hot attic (peak conditions; 120 oF and 30% RH) can
                    produce a 16% reduction in cooling output and 20% increase
                    in cooling energy use (Cummings and Tooley, 1989), and this
                    was only from the air handler and adjacent connections. (Figure
                    64)  
 “Total” Duct Leakage  
 Some important observations were made from the extended
                    test data in 20 houses. Total leakage on the return side
                    of the system (including the air handler and return connection)
                    was 53 cfm with weighted operating pressure on the return
                    side of about -100 Pa (including the air handler), operating
                    return leakage was calculated to be 122 CFM, or 9.7% of the
                    rated system air flow.  
 Total leakage on the supply side of the
                      system (Q 25s,total) was very large, at 134. The ASHRAE
                      152P method suggests using half of the supply plenum pressure
                      as an estimate of the overall supply ductwork operating
                      pressure, if the actual duct pressures are not known. For
                      the 20 systems with extended testing, supply plenum pressure
                      was 73.3 Pa. Based on a pressure of 37 Pa, actual leakage
                      should be 167 CFM or about 13.3% of the rated air flow.
                      To test the ASHRAE divide-by-two method, supply duct operating
                      pressure measurements were taken from 14 representative
                      systems. These averaged 35.9 Pa, compared to 65.7 Pa for
                      the supply plenums for those same 14 systems. For these
                      systems, the duct pressure was 55% of the supply plenum
                      pressure - making the ASHRAE method a reasonable method
                    for estimating central Florida home’s supply ductwork
                    operating pressures.  
 However, the ASHRAE method wasn’t reasonable for
                    estimating central Florida home’s return ductwork operating
                    pressures. For these 20 systems, 38% of the Q 25r,total was
                    in the air handler and 62% of the Q 25r,total was in the
                    return ductwork. Given an air handler pressure of -133 Pa,
                    a return plenum pressure of -81.5 Pa, and return duct pressure
                    of approximately -70 Pa, the weighted return side pressure
                    was approximately -95 Pa. By contrast, the ASHRAE method
                    predicted -41 Pa. Clearly, in systems with a single, short
                    return duct plenum like those commonly found in Florida,
                    the actual operating pressure should be greater than the
                    return plenum, maybe by as much as 1.2 times the plenum pressure.  
 Return side leakage is available on 58 of the 69 systems.
                    Return leak air flow (Q r,total) combined for the air handler,
                    return connection, and the return ductwork was found to be
                    152.4 CFM, or 11.8% of total rated system air flow for this
                    group. For this larger sample, Q r,total is considerably
                    greater than for the 20 houses with extended testing. These
                    alarming results show that even in these newly constructed
                    homes about 12% of return air and 13% of supply air duct
                    systems are leaking.  
 Duct Leakage to “Out”:  
 In 20 homes, duct leakage to “out” was
                      measured. (Table
                      38) On average, 56% of the leakage of the return ductwork
                      and supply ductwork was to “out.” “Out” is
                      defined as outside the conditioned space, including buffer
                      spaces like an attic or garage. The fraction of leakage
                      that was to “out” varied by air handler location.
                      For return ductwork, the proportion of total leakage to “out” is
                      81.4% for attic systems, 67.6% for garage, and 28.0% for
                      indoors. For supply ductwork, the proportion of total leakage
                      to “out” was in the range of 52% to 56% for
                      all three locations.  
Table
                            38 Portion of duct leakage to outdoors [(Q 25,out/Q
                            25,total) * 100].   | 
 
Air Handler Location  | 
Return  | 
Supply  | 
Entire Duct System  | 
 
Attic  | 
81.4%  | 
56.5%  | 
63.2%  | 
 
Garage  | 
67.6%  | 
51.7%  | 
56.0%  | 
 
Indoors  | 
28.0%  | 
52.6%  | 
37.1%  | 
 
 
 The attic return ductwork was the most predictive
                      variable to “out” leakage findings. All of
                      the return ductwork for attic units was located in the
                      attic. Much of the return ductwork for other units was
                      located in the house. As a consequence, the energy penalty
                      associated with locating the air handler in the attic was
                      greater than indicated in the computer modeling results
                      in Table 39, since the modeling only considered the leakage
                      of the air handler cabinet and the adjacent connections,
                      and not the return ductwork leakage.  
Table
                              39 Duct leakage “total” and
                                    to “out” for three locations,
                                    for both 25 Pa test pressure and for actual
                                    system operating pressure. Sample size is
                              in [brackets].   | 
 
 | 
Attic
                            (cfm)  | 
Garage
                            (cfm)  | 
Indoors
                            (cfm)  | 
Combined
                            (cfm)  | 
 
Test  | 
Total  | 
Out  | 
Total  | 
Out  | 
Total  | 
Out  | 
Total  | 
Out  | 
 
Q 25,r [58]  | 
61.9  | 
50.4  | 
93.3  | 
63.1  | 
67.8  | 
19.0  | 
75.7  | 
44.9  | 
 
Q 25,s [20]  | 
109.1  | 
61.6  | 
170.6  | 
88.2  | 
119.5  | 
62.9  | 
134.3  | 
71.4  | 
 
Q r [58]  | 
118.1  | 
96.1  | 
194.4  | 
131.4  | 
134.6  | 
37.7  | 
152.4  | 
90.4  | 
 
Q s [20]  | 
135.6  | 
76.6  | 
212.0  | 
109.6  | 
148.5  | 
78.1  | 
166.9  | 
88.7  | 
 
 
 Table
                      39  shows that the operating supply leakage to “out” was
                      large for all three air handler locations, averaging 89
                      CFM. The average operating return leakage to “out” was
                      slightly larger, at 90 CFM. However, there was a large
                      variation between air handler locations; 96 CFM for attic
                      systems, 131 CFM for garage systems, but only 38 CFM for
                      indoor systems. From an energy perspective, the attic systems
                      experienced the greatest “real” energy penalties,
                      because all of the return ductwork and air handlers were
                      located in the attic. (Table 38) By contrast,
                      a majority of the return leakage for the garage systems
                      likely came from the garage (which is considerably cooler
                      than the attic). For indoor systems, the return leakage
                      to “out” most likely originated from the attic.
                      However, since the return leakage was so much smaller,
                      the energy impact was likely considerably less than both
                      the attic and the garage systems.  
 | 
 
  Figure
                                65 Supply
                            CFM25 “total” leakage versus the number
                    of supply registers.   | 
 
 | 
 
  Figure
                                66  Supply
                            CFM25 “out” leakage  
                            versus the number
                    of supply registers.   | 
 
 
Correlation
                        of Supply Duct Leaks with Number of Registers: When
                    analyzing the supply leakage in the extended test data, a
                    surprising correlation was observed. This correlation indicated
                    a systematic and consistent duct fabrication problem across
                    a wide range of air conditioning contractors. Figure
                    65 illustrates this correlation, showing that each supply
                    duct has a remarkably predictable total duct leakage. The
                    coefficient of determination is 0.86, indicating that 86%
                    of the variability in total supply duct leakage was explainable
                    by the number of supply registers. Figure 66 shows
                    a similar relationship between supply leakage to “out” and
                    the number of supply registers. In this case the coefficient
                    of determination was 0.69, indicating that 69% of the variability
                    in total supply duct leakage was explainable by the number
                    of supply registers. Note that one of the two houses with
                    13 registers showed considerably less leakage than expected.
                    In this case, supply ducts were located in the interstitial
                    space between floors. When the house was taken to -25 Pa,
                    it is probable (though not measured) that the interstitial
                    spaces were substantially depressurized as well, so leaks
                    in those supply ducts would show less air flow (i.e., less
                    pressure differential = less leakage air flow) and therefore
                    be under-represented.  
The data suggest that a duct leakage problem occurs in nearly
                    all new homes. Researchers identified three issues that create
                    most of the leakage: (1) the connection of the supply register
                    or return grill (Figure 68), (2) the boot (supply
                    box) to sheet rock connection (Figure 67), and (3)
                    the flex duct to collar connection. The supply register or
                    return grill leakage typically shows as supply leakage in
                    the “total” test.
                    It usually occurs when the register or grill does not fit snugly
                    to the ceiling or wallboard. Issues two and three show up as
                    leakage to both “out” and “total.”
 
 | 
 
 Figure 67 Flexible duct
                             
                      to metal collar connection.   | 
 
 | 
 
 Figure 68 Gaps at the
                      supply  
                      register to drywall joint   | 
 
 
Figure
                      67 shows how flexible duct connections typically are
                      made. In some cases metal tape is used, but the tape wrinkles
                      when applied to complex angles and over bumps associated
                      with these connection types. Although small in size, these
                      cumulative wrinkles at each connection allow air to pass
                  through.  
 Computer
                    Modeling for Florida Energy Code Air Handler Multipliers:  
 FSEC
                      researchers performed simulations and developed air handler
                      multipliers for the Florida Energy Code using this study’s
                      simulation results. Researcher used the FSEC 3.0 model,
                      a general building simulation program developed in 1992.
                      This program provided simultaneous detailed simulations
                      of a whole building system, including energy, moisture,
                    multi-zone air flows, and air distribution systems.  
 In 2001, modeling had been performed to develop initial
                    air handler multipliers. These multipliers were based on
                    estimated Q 25 and duct operating pressures. At the time
                    of the 2001 modeling, there was essentially no data on air
                    handler and connection leakage. Modeling for this project
                    was performed again, but this time using the results of the
                    69 field tested homes.  
 The modeling inputs used in 2001 and those from the current
                    study are shown below. (Table 40) Note that the
                    same Q 25 and operating depressurization (dP) values was
                    used for all air handler locations, since there was essentially
                    no difference between the Q 25 values for attic, garage,
                    and indoor air handler locations when gas furnace units were
                    removed from the analysis.  
Table
                            40 Air handler (AH) and connection inputs  
                          for 2001
                        and current project computer
                            modeling.  
 | 
 
 | 
2001 Q 25  | 
AH Study Q 25  | 
2001 dP  | 
AH Study dP  | 
 
Return connection  | 
8.7  | 
3.9  | 
-40  | 
-86.1  | 
 
AH – depressurized
                          portion  | 
48.5  | 
17.6  | 
-42  | 
-139.1  | 
 
AH – pressurized
                          portion  | 
9.6  | 
2.8  | 
43  | 
106.5  | 
 
Supply connection  | 
7.8  | 
1.6  | 
32  | 
58.2  | 
 
Total  | 
74.6  | 
25.9  | 
 | 
 
 
While
                      the Q 25 leakage for the air handler and connections was
                      about 65% less than earlier estimates, operating pressures
                    were much higher. The air handler multipliers based on the
                    current computer modeling results are presented in Tables
                    41, 42, and 43. Modeling of air handler energy use also
                    was performed for the air handlers located outdoors, despite
                    the fact that no field data was collected for outdoor units.
                    The modeling input parameters were the same as the other
                    air handler locations as shown in Table 40. Note
                    also that the air handler multipliers for the attic, indoors,
                    and outdoors are normalized to the garage, since this location
                    was considered the baseline. The final report for this study
                    can be viewed online at: http://www.fsec.ucf.edu/bldg/pubs/cr1357/index.htm.  
Table
                            41 Florida Energy Code AH Multipliers for South Florida.   | 
 
  
AH Location  | 
Winter  | 
Summer  | 
 
Old  | 
2001  | 
new  | 
old  | 
2001  | 
new  | 
 
attic  | 
1.04  | 
1.15  | 
1.12  | 
1.04  | 
1.09  | 
1.06  | 
 
garage  | 
1.00  | 
1.00  | 
1.00  | 
1.00  | 
1.00  | 
1.00  | 
 
indoors  | 
0.93  | 
0.91  | 
0.94  | 
0.93  | 
0.91  | 
0.92  | 
 
outdoors  | 
1.03  | 
1.08  | 
1.06  | 
1.03  | 
1.03  | 
1.01  | 
 
 
 
Table
                            42 Florida Energy Code AH Multipliers for Central
                            Florida.   | 
 
  
AH Location  | 
Winter  | 
Summer  | 
 
Old  | 
2001  | 
new  | 
old  | 
2001  | 
new  | 
 
attic  | 
1.04  | 
1.11  | 
1.08  | 
1.04  | 
1.10  | 
1.08  | 
 
garage  | 
1.00  | 
1.00  | 
1.00  | 
1.00  | 
1.00  | 
1.00  | 
 
indoors  | 
0.93  | 
0.92  | 
0.94  | 
0.93  | 
0.90  | 
0.92  | 
 
outdoors  | 
1.03  | 
1.09  | 
1.05  | 
1.03  | 
1.02  | 
1.01  | 
 
 
 
Table
                            43 Florida Energy Code AH Multipliers for North Florida.   | 
 
  
AH Location  | 
Winter  | 
Summer  | 
 
Old  | 
2001  | 
new  | 
old  | 
2001  | 
new  | 
 
attic  | 
1.04  | 
1.10  | 
1.03  | 
1.04  | 
1.11  | 
1.08  | 
 
garage  | 
1.00  | 
1.00  | 
1.00  | 
1.00  | 
1.00  | 
1.00  | 
 
indoors  | 
0.93  | 
0.93  | 
0.94  | 
0.93  | 
0.91  | 
0.92  | 
 
outdoors  | 
1.03  | 
1.07  | 
1.02  | 
1.03  | 
1.02  | 
1.01  | 
 
 
- Air Conditioning Condenser Fan Efficiency 
 
 
Purpose  
The purpose of this study is to develop an air conditioner
                    condenser fan that reduces the electric energy use of the
                    condensing unit (Figure 69). To accomplish this,
                    researchers are designing and producing more aerodynamic
                    fan blades and substituting smaller horsepower (HP) motors
                    which achieve the same air flow rates as the larger, less
                    efficient motors typically used. 
 4th
                      Budget Period  
 | 
 
 Figure 69  Air conditioning
                             
                      condenser fan and diffuser.   | 
 
  During
                      the 4th budget period, researchers developed baseline data
                      for the fan power use in a standard condensing unit (Trane
                      2TTR2036) and tested a new prototype design: “Design
                    A5” with five asymmetrical blades 
Baseline
                      data included condenser airflow, motor power, sound levels,
                      and condenser cabinet pressures. Test results favorably
                      compared with the manufacturer’s test data. An experimental
                    set of fan blades, “Design-A5,” designed for
                    a 1/8 hp motor at 850 rpm was numerically created and then
                    successfully produced using rapid prototyping. These prototype
                    blades were substituted on the original condenser, and all
                    test measuredments were redone. Design-A5 was found to reduce
                    power use by 20% (40 watts) with approximately equivalent
                    airflow to the original condensing blade design.  
 5th
                      Budget Period  
During the 5th budget period, activities included re-calibration
                    and improvement of the test equipment configuration, refinement
                    of various designs, and patent filing. 
Re-calibration and Improvement of Test Equipment Configuration  
The
                      air flow measurement equipment was re-calibrated by the
                      Energy Conservatory in Minneapolis in accordance with ANSI/ASHRAE
                      51-1985 ("Laboratory Methods of Testing
                    Fans for Rating."). Testing determined that the "flow
                    cube" could be modified with settling screens and a
                    flow straightener to yield a 5% absolute flow accuracy and
                    a 2% relative accuracy from the test equipment. Also, the
                    test configuration was moved indoors in order to better measure
                    sound and also to reduce test variability from wind-related
                    effects. Noise measurement protocol improved to comply with
                    procedures used by the air conditioning industry.  
Continued Testing to Refine the Identified Condenser
                      Fan and Condenser Top Design  
All
                      fans were re-evaluated after bringing the test apparatus
                      into compliance with ANSI/ASHRAE 51-1985 ("Laboratory
                    Methods of Testing Fans for Rating.") New fan prototypes “Design-D” and “Design
                    E” were tested as well as a diffuser for a 27" fan
                    and a specially prepared Electronically Commutated Motor
                    (ECM) provided by General Electric. 
All designs were also tested with the conical diffuser with
                    20-27% increases in measured flow from the low rpm designs,
                    which use 8-pole motors. Sound measurements (Table 44) also
                    showed large advantages with as much as a 4 dB reduction
                    in fan sound level over the standard fan. The final test
                    prototype with diffuser and fan is shown in Figure 70.  
 Table
                            44 Sound measurements for various fan and housing
                            designs   | 
 
 Top   | 
 Fan   | 
 Motor   | 
 Flow   | 
 Power   | 
 Sound   | 
 
 OEM/ Starburst   | 
 OEM   | 
 6-pole   | 
 2170 cfm   | 
 197 W   | 
 63.0 dB   | 
 
 OEM-Foam   | 
 OEM   | 
 6-pole   | 
 2230 cfm   | 
 198 W   | 
 63.0 db   | 
 
 Wire top   | 
 OEM   | 
 6-pole   | 
 2180 cfm   | 
 188 W   | 
 62.0 dB   | 
 
 Wire-Foam   | 
 OEM   | 
 6-pole   | 
 2250 cfm   | 
 190 W   | 
 62.0 db   | 
 
 OEM-foam   | 
 A5   | 
 8-pole   | 
 1945 cfm   | 
 145 W   | 
 62.0 dB   | 
 
 Wire-foam   | 
 A5   | 
 8-pole   | 
 2110 cfm   | 
 146 W   | 
 60.0 dB   | 
 
 WhisperGuard w/foam   | 
 A5   | 
 8-pole   | 
 2300 cfm   | 
 143 W   | 
 58.5 dB   | 
 
 
Presentation and Commercialization  
In January, BAIHP researcher Danny Parker made a presentation
                    at the DOE Expert meeting on HVAC and Fans in Anaheim, California
                    and participated in productive meetings with Trane Corporation
                    in May 2004 to discuss licensing of the technology under
                    an existing non-disclosure agreement. 
Patents Pending  
U.S.
                      Application Serial No. 10/400,888, Provisional applications
                      60/369,050 / 60/438,035 & UCF-449CIP;
                      WhisperGuard (UCF-Docket No. UCF-458) 
Key
                          Improvements from WhisperGuard Technology 
 | 
 
 Figure
                                  70 Final
                                  test prototype 
        with diffuser and fan.  | 
 
  Tested Performance with Trane TTR2036 Condenser: 
- Provides 46 Watt reduction in fan power (144 W vs. 190
                      Watts)
 
- Increases condenser air flow by 130 cfm (6% increase
                        in fan flow)
 
- Provides 102 W power reduction with ECM 142 motor 
 
- Reduce ambient fan-only sound level by 4-5 dB
 
- ECM motor allows lower fan speeds for ultra-quiet night
                      operation, higher flows for maximum capacity during very
                      hot periods (temperature based control)
 
- Attractive hi-tech diffuser appearance
 
 
Key
                      Technologies Employed  
- High efficiency 5-bladed asymmetrical fan moves air quietly
                      at lower fan speeds
 
- Diffuser top for effective pressure recovery increasing
                      air flow at slow speed ranges
 
- Conical center body reduces exhaust swirl
 
- Acoustic
                      sound control strip to reduce tip losses and control tip
                        vortex shedding
 
 
 
- 
 Fenestration Research
 
 
 American
                          Society of Heating, Refrigerating, and Air Conditioning
                  Engineers (ASHRAE) Technical Committee :  
 In 2002, BAIHP researchers wrote a statement of work for
                    the development of a methodology to calculate solar spectral
                    distributions incident on windows for various sun positions
                    and atmospheric conditions. ASHRAE approved the project and
                    sent it out for bid. Completion of this work project should
                    make it much easier to determine the true solar heat gain
                    through spectrally selective fenestration systems for varying
                    atmospheric conditions and solar altitude angles.  
 Calorimetric Measurements of Complex Fenestration Systems  
 FSEC’s
                      research calorimeter will be used both indoors with the
                      FSEC Vortek solar simulator and outside under natural solar
                      radiation, on its Sagebrush solar tracker, for window solar
                      heat gain experiments. The results of this testing will
                      offer a way to test the solar gain properties of complex
                      and other non-standard fenestration options for industrialized
                      housing, such as exterior and interior shades and shutters,
                    and those placed between the panes of double pane windows.  
 Sagebrush Solar Tracker  
 The
                      computer program running the calorimeter, the Sagebrush
                      tracker, and both together is complete. It contains a user-friendly
                      graphic interface and offers a wide variety of experimental
                      opportunities. There are many channels for adding additional
                      temperature sensors and the calorimeter/tracker can be
                      operated with either the sun as a source - in a variety
                    of tracking modes - or with FSEC’s Vortek solar simulator.  
 To
                    conduct outdoor testing, the Neslab chiller must be connected
                    to the flow meter, the temperature sensors to the calorimeter,
                    and the calorimeter mounted on the tracker. The Sagebrush
                    tracker now is functional, responding properly to commands
                    sent from the computer, rotating in altitude, and azimuth
                    and stopping when the limit switches are encountered. A telescopic
                    sight and level for positioning it outdoors in the proper
                    orientation for accurate solar tracking has been designed
                    and is near fabrication completion.  
 | 
 
 Figure 71  Side view
                            of calorimeter before  
                          it was mounted on the Sagebrush
                    Tracker.   | 
 
 
The
                      Neslab chiller and remote controller have been connected
                    to a Gateway laptop computer and a RS-485 serial interface
                    card necessary to operate the calorimeter has been installed.
                    Researchers can now send commands and receive data from the
                    chiller. Although the calorimeter is designed to work directly
                    with the existing FSEC hydronic loop used for testing solar
                    collectors, the Neslab will give an independent, standalone
                    capability to the calorimeter. (Figure 71) 
 The water flow meter purchased for measuring the flow into
                    the calorimeter has been successfully connected to the Agilent
                    (HP) 34970A data acquisition system and its measurements
                    were incorporated into the calorimeter operating program.
                    Temperature sensors also successfully connected to the data
                    acquisition system, are reading properly, and have been incorporated
                    into the calorimeter program. The program has coding to include
                    a number of additional temperature channels once the temperature
                    probes have been received and installed in the calorimeter.
                    Another 20-channel input card is being purchased for the
                    Agilent, to permit additional temperature readings. Knowing
                    the flow rate and temperature difference, the heat delivered
                    to the water by the calorimeter can now be accurately determined.  
 Now that all portions of the system are operational, researchers
                    will configure the outdoor system, verify, and begin testing
                    in Year 5.  
 Vortek Solar Simulator  
 In
                      2003, the Vortek Simulator was fired up and operated reliably
                      on the calorimeter testing with FSEC’s solar
                    collector test apparatus. As expected, a few computer and
                    other problems delayed initial data collection by a couple
                    of days. However, these problems were corrected and testing
                    proceeded normally.  
 During
                      testing, the calorimeter was connected to the existing
                      facility’s hydronic loop, which was
                      developed over a period of years to a temperature stability
                      of 0.01 degrees centigrade. The irradiance level measured
                      about 820 watts per square meter over an aperture of 0.557
                      square meters. The calorimeter was tested as though it
                      were a flat plate collector, to obtain its efficiency curve.
                      This was used to infer the thermal losses and solar heat
                      gain coefficient of the eighth inch clear single pane of
                      glass used for the test. The nominal wind speed was set
                      by the laminar blower to five miles per hour. The coolant
                      flow was run at levels of 0.2, 0.5, and 1.0 gallons per
                    minute (GPM), and at varying inlet temperatures.  
 For all test runs, steady state conditions were established
                    by observing the outlet temperature in a real-time plot as
                    equilibrium was approached. During periods of non-equilibrium,
                    the recorded data was used to measure the first-order system
                    time constant, a function of the flow rate. The calorimeter
                    time constant varied from 1.5 minutes at 1.0 GPM to 6.9 minutes
                    at 0.2 GPM. These time constants were obtained by blocking
                    the incident beam and watching the decay in outlet temperature.  
 Skylight Dome Transmittance  
 Researchers completed work on the skylight dome transmittance,
                    adding a spherical shape to the cylindrical one previously
                    used. The ray tracing programming was changed to eliminate
                    reflection of rays approaching the dome from the inside,
                    for comparison with the analytical model, which does not
                    yet include internal reflections. The difference between
                    the two computational approaches, at a 30 E solar zenith
                    angle is 1.7%, considered acceptable for rating skylight
                    performance.  
 With both cylindrical and spherical dome models, transmittance
                    at large solar zenith angles above 60 is substantially greater
                    than for a horizontal flat plate. This is because most of
                    the rays incident on the dome and entering the skylight are
                    incident on the dome close to perpendicular, where dome transmittance
                    is highest.  
 Energy Gauge USA and Energy Gauge FlaRes  
 BAIHP mapped a table of window and shade characteristic
                    simulations that could be run with these two programs. These
                    runs will be used to determine the energy use of various
                    fenestration options for Florida residences and to guide
                    the preparation of instructional materials.  
 Florida Market Transformation 
 From the beginning of the BAIHP program, researchers have
                    provided technical background information and support to
                    the Alliance to Save Energy and the Efficient Windows Collaborative
                    to promote the sale and installation of energy efficient
                    fenestration in hot climates (such as Florida) and other
                    areas for both conventional and industrialized homes. BAIHP
                    also provides advice, technical information, and educational
                    information to energy companies regarding window energy performance.  
 National Fenestration Rating Council (NFRC) Technical
                      Committee 
 In 2002, BAIHP presented a final report at a Task Group
                    meeting in Houston, on the NFRC- funded work to develop a
                    draft standard practice for the rating of tubular daylighting
                    devices. That project is now complete.  
 In
                      2001, BAIHP researchers performed a number of ray traces
                      on a highly reflective cylinder of varying lengths, using
                      the trace results to determine the cylinder’s transmittances
                    for different interior surface reflectivities (from 90% to
                    100%). These results generated a “default table” for
                    determining the transmittance of this tubular daylighting
                    component. Using simplified assumptions, and then multiplying
                    the tube transmittance by the top and bottom dome transmittance
                    results, researchers determined the total transmittance for
                    a chosen sun angle. Based on the findings, BAIHP provided
                    NFRC and the industry with a list of suggested research projects
                    to test and develop this methodology further. One of these
                    submitted projects was sent out for bid by ASHRAE in Year
                    4 and is expected to begin in Year 5.  
 Tubular Daylighting Device SHGC and VT Value Calculations  
 Following
                      a request from the TDD industry, a sequence of operations
                      and a new computer program were written to access the Window
                      5 glazing database and obtain from it the spectral transmittance
                      and front and back reflectance data for any sheet of glazing
                      in that database which might be used in making the top
                      dome of a tubular daylighting device. This permits determination
                      of the input parameters needed to run TDDTrans. The computer
                      program was posted for free download and is available by
                      clicking on http://fsec.ucf.edu/download/br/fenestration/software/TddTrans-Beta/TDDTrans.exe.  
 Access sequence:  
-  Download and run the Optics 5 program. 
 
-  Select the glazing to be used in the tubular daylighting
                      device. 
 
-  Export its spectral data file as a standard ASCII text
                      file.
 
 
  |